 |
|
• The use of dot matrix system color LCD
• Touch panel contributes to user friendliness
• Equipped with pump control output, alarm output and transmission output (for recording)
• Equipped with an automatic calibration and a sensor diagnosis function
• Includes the RS-485 interface as standard equipmen
• Includes logging facility as standard equipmen
• Multi-voltage (AC90-240V) |
Example of control <pH control>
 |
|
Stroke rate of electromagnetic metring pumps (P1, P2) are controlled corresponding to signal of pH sensor Point A and B of P1 and P2 can be adjusted optionally. Upper limit spm can be set by upper mode setting mode. Note: pH is replaced with mV for ORP.
 |
Specifications
| Model |
PH-100W |
OR-100W |
| Measuring range |
PH0.00 to 14.00 Resolution: 0.01pH |
ORP 2000mV Resolution: 1mV |
| Control output |
Pulse PID control or ON/OFF control Potential free contact 1ax 2 (AC/DC 200V 0.2A) |
| Transmission output |
DC 0 to 20mA (To be set optionally) Load resistance 500 or below Insulation type |
| Input signal |
• For level switch potential free contact input x2 • DC 4 to 20 mA |
| Output alarm |
Upper limit alarm, Lower limit alarm, Output set point attained, Abnormal sensor signal, Abnormal level signal, Abnormal external signal Potential free 1ax 4 (Resistance load AC250V 10A DC30V 10A) Any four items from the 7 items can be set to AL1 to AL4 |
| Function |
Automatic calibration (One point, two points calibration JIS pH4/7/9) Manual calibration (One point, two points calibration) Sensor diagnosis function (Abnormal temp. sensor, Abnormal buffer, Abnormal response speed, Abnormal sensibility, Abnormal asymmetry potential) Error message (Calibration error, Beyond measuring range) Measuring value shift function (pH2.00) |
| Power source |
AC90 to 240V 50/60Hz 25VA |
| Insulation resistance |
100MΩ at DC500V |
|
• Magnetic drive pumps • Metering pumps
& dosing pumps • Pneumatic drive pumps • Air pumps • Gear pumps • Turbine pumps • Screw pumps
• Water quality control
|
|