Superior operability & ample control configurationEconomical water treatment controller
※In order to download information materials and catalogues, you need to register a user
account (for free) with us. Membership Registration
The P100 / W100 series is a water treatment controller that has a multilingual display function and excellent operability. Although it is an economical entry model, it can be widely used at all water treatment sites such as cooling towers, hydroponic cultivation, and pools with abundant control settings. The large display and easy-to-read icons make it easy to set up.
Note: P100=4 points, W100=3 points
Simple pH neutralization control (P100), small-scale cooling tower control with one-component control (W100), etc.
Model | P100 WPHNP120A |
W100 WJPHNW120HA-N |
|
---|---|---|---|
Application | For the pH Sensor and ORP Sensor without amplifier | ||
Measurement | pH |
Measuring range: 0.00 to 14.00 pH (Display range: -2.00 to 16.00 pH) |
|
Resolution: 0.01 pH | |||
Repeatability: ±0.05 pH (per controller) | |||
ORP | Measuring range: ±1,500.0 mV | ||
Resolution: 0.1 m | |||
Repeatability: ±5 mV (per controller) | |||
Temperature | Measuring range: 0.0 – 120.0°C (Display range: -5.0 – 260.0°C) Resolution: 0.1°C Linearity: F.S±1% (per controller) |
||
Cumulative flow into a low-speed flowmeter | Max frequency: 10 Hz (Duty 50:50) Cumulative range: 0 to 1,000,000,000 Meter factor: 0 to 100,000 lit, gal, m3 Unit: lit, gal, m3 |
||
Cumulative flow into a high-speed flowmeter | Max frequency: 500 Hz (Duty 50:50) Cumulative range: 0 to 1,000,000,000 Pulse constant: 0.00 to 100,000.00 pulse/lit, gal, m3 Unit: lit, gal, m3 |
||
Instant flow into a high-speed flowmeter | Max frequency: 500 Hz (Duty 50:50) Display range: 0.00 to 21,474,836.47 Pulse constant: 0.00 to 100,000.00 pulse/lit, gal, m3 Unit: l/sec, l/min, l/hour, l/day, gal/sec, gal/min, gal/hour, gal/day, m3/sec, m3/min, m3/hour, m3/day |
||
Input | pH input | Glass film electrode (without amplifier) | |
ORP input | ORP electrode (without amplifier) | ||
Temperature | Pt 100, Pt 1,000 (freely selectable), automatic temperature compensation | ||
Contact | No voltage contact signalNote1×1 | No voltage contact signalNote1×2 | |
Interlock, low-speed flowmeter, high-speed flowmeter (freely selectable) | |||
Output | Relay | • No voltage contact x 2 1a 250 VAC 8A (resistance load) • Semiconductor contact x 2 1a 48 VAC/DC 0.5A for the pulse control of pumps |
• No voltage contact x 1 1a 250 VAC 6A (resistance load) • Semiconductor contact x 2 1a 40 VAC/DC 0.2A for the pulse control of pumps |
Transmission | • DC4 to 20 mA against the measured value (freely selectable) Load resistance: 600Ω or lower, isolated • Accuracy: F.S±1% |
||
Power supply voltageNote2 | AC100 to 240V, 50/60Hz |
Model | P100 WCNP110A/120A |
W100 WJCNW120HA-N |
|
---|---|---|---|
Application | For the General-purpose Conductivity Sensor | ||
Measurement | Two-electrode conductivity |
Measuring range: 0.000 to 30.000 mS/m (cell constant: 0.01), 0.00 to 300.00 mS/m (cell constant: 0.1), 0.0 to 3,000.0 mS/m (cell constant: 1), 0 to 30,000 mS/m (cell constant: 10) | |
Resolution: 0.001 mS/m, 0.01 mS/m, 0.1 mS/m, 1 mS/m | |||
Linearity: F.S±1% (per controller) | |||
Electro- magnetic conductivity |
Measuring range: 50.0 to 1,200.0 mS/m, 300.0 to 4,000.0 mS/m, 1,000 to 15,000 mS/m, 5,000 to 50,000 mS/m, 20,000 to 200,000 mS/m (freely selectable) (Display range: 0 to 1,600.0/5,332.0/19,995/66,650/266,600 mS/m) |
||
Resolution: 0.1 mS/m, 1 mS/m | |||
Linearity: F.S±1% (per controller) | |||
Temperature | Measuring range: 0.0 – 120.0°C (Display range: -5.0 – 260.0°C) Resolution: 0.1°C Linearity: F.S±1% (per controller) |
||
Cumulative flow into a low-speed flowmeter | Max frequency: 10 Hz (Duty 50:50) Cumulative range: 0 to 1,000,000,000 Meter factor: 0 to 100,000 lit, gal, m3 Unit: lit, gal, m3 |
||
Cumulative flow into a high-speed flowmeter | Max frequency: 500 Hz (Duty 50:50) Cumulative range: 0 to 1,000,000,000 Pulse constant: 0.00 to 100,000.00 pulse/lit, gal, m3 Unit: lit, gal, m3 |
||
Instant flow into a high-speed flowmeter | Max frequency: 500 Hz (Duty 50:50) Display range: 0.00 to 21,474,836.47 Pulse constant: 0.00 to 100,000.00 pulse/lit, gal, m3 Unit: l/sec, l/min, l/hour, l/day, gal/sec, gal/min, gal/hour, gal/day, m3/sec, m3/min, m3/hour, m3/day |
||
Input | 2-electrode conductivity input | 2-electrode conductivity sensor, cell constants: 0.01, 0.1, 1, 10 | |
Electromagnetic conductivity input | Electromagnetic conductivity sensor | ||
Temperature | Pt 100, Pt 1,000, 10-k thermistor, 100-k thermistor (freely selectable), automatic temperature compensation | ||
Contact | No voltage contact signalNote1×1 | No voltage contact signalNote1×2 | |
Interlock, low-speed flowmeter, high-speed flowmeter (freely selectable) | |||
Output | Relay | • No voltage contact x 2 1a 250 VAC 8 A (resistance load) • Semiconductor contact x 2 1a 48 VAC/DC 0.5 A, for the pulse control of pumps |
• No voltage contact x 1 1a 250 VAC 6A (resistance load) • Semiconductor contact x 2 1a 40 VAC/DC 0.2A for the pulse control of pumps |
Transmission | • DC4 to 20 mA against the measured value (freely selectable) Load resistance: 600Ω or lower, isolated • Accuracy: F.S±1% |
||
Power supply voltageNote2 | AC100 to 240V, 50/60Hz |
Note1: The max applied voltage is DC 9 V, and the max applied current is 2.3 mA to the contact. Use a component of the min applied load of 1 mA or lower as a contact component, such as a relay.
Note2: Do not apply any voltage that is outside the specifications; doing so may cause failure. Note that the allowable voltage ranges from AC 90 to 264 V.
• Ambient temperature: 0 to 45°C
• Ambient Humidity: 35% to 85% RH; with no condensation in the controller
• Storage temperature: -20 to 80°C
• Installation conditions: No exposure to direct or reflected sunlight
pH • ORP sensor
• Excellent corrosion resistance and temperature resistance.
• Internal liquid non replenishment type.
• The electrode part is easy maintenance.
• There are three types of electrode structures.
• Internal liquid replenishment type.
• Less clogging at the liquid junction and long life.
• It is ideal for process applications such as waste water treatment and surface treatment.
Conductivity sensor
• Measurement range*: 0.0〜3000.0mS/m, 0.00〜300.00mS/m, 0.000〜30. 000mS/m
• Operating temperature: 5〜45℃
• Temperature sensor: Pt1000 Ω
*Indicates the range when used with the W100 series or Intuition-6 series; these are not the performance of a stand-alone sensor itself.
• Measurement range: 0〜200S/m
• Operating temperature: 0〜60℃*
• Temperature sensor: Pt1000 Ω
*This varies depending on the types and concentrations of liquid used.